Table 3-6. Summary of CEM Test Results from T. H. Wharton Unit 41 HRSG Inlet


                               System      O2    CO2      CO(a)       Flow Rate   Flow Rate
 Date    Run #   Sample Time   To FTIR    (%d)   (%d)   ppmd  lb/hr    (wscfm)     (dscfm)
-------  -----   -----------  ---------   ----   ----   ----  -----   ---------   ---------
5/17/93    1      1804-1939    Hot/Wet    15.1    3.3    1.8    2.8    413,521     359,763

5/18/93    2      1140-1208    Hot/Wet    15.1    3.3    2.3    3.7    418,557     364,145
                  1226-1431   Condenser   15.1    3.3    1.9    3.0

5/18/93    3      1521-1624   PermaPure   15.1    3.4    2.4    3.9    433,541     377,181
                  1635-1654    Hot/Wet    15.1    3.4    2.7    4.4

        (a)  The CO emissions rates were calculated using dry basis
             concentrations and flow rate data.