Technology Transfer Network
Geographic / Ecosystems Initiatives
Oregon Clean Energy Center
- Name of the facility:
Oregon Clean Energy Center
- Location:
816 Lallendorf Rd.
Oregon, Ohio 43616
Lucas County
- Distance from the US/Canada border:
Approximately 40 km
- Type/size of the facility:
844 megawatt (gross) electric generating facility
- Source of emissions:
Two natural gas-fired combined cycle combustion turbines (2,936 mmBtu/hr heat input each) with heat recovery steam generators (300 mmBtu/hr heat input duct burner each), 99 mmBtu/hr heat input natural gas-fired auxiliary boiler, 2,250 kW emergency diesel-fired generator, 223.8 kW emergency fire water pump, 16-cell mechanical draft wet cooling tower
- Type of fuel:
Natural gas for: turbines, duct burners and boiler; ultra-low sulfur diesel fuel for emergency generator and fire water pump
- Type/quantity of mass emission rates:
Pollutant Tons/yr CO 193 NOx 193 PM10 128 PM2.5 124 SO2 38 VOC 79 H2SO4 13 GHG 2,966,778 Ammonia 173
- Emission control technology
Turbines/duct burners
Dry low NOx burners, SCR, catalytic oxidizerEmergency diesel generator and fire pump
Maximum annual usage of 500 hours eachAuxiliary boiler
Low NOx burners with flue gas re-circulation, maximum 2,000 hours/yr operationCooling tower
Mist eliminator, total dissolved solids restriction
- Date permit application received:
8/1/2014
- Stack height and diameter:
Common heat recovery steam generator stack
stack height: 240 ft
inside diameter: 22 ftAuxiliary boiler
stack height: 240 ft
inside diameter: 4 ftCooling Tower (11-cell)
stack height: 46 ft (each)
inside diameter: 33 ft (each)Emergency generator
stack height: 53.5 ft
inside diameter: 0.78 ftEmergency fire pump
stack height: 30 ft
inside diameter: 0.67 ft
- Permit agency's contact name, address, telephone number:
Mike Hopkins
Ohio Environmental Protection Agency
Lazarus Government Center
50 West Town Street, Suite 700
Columbus, OH 43215
(614) 644-3611