Jump to main content or area navigation.

Contact Us

Technology Transfer Network
Emission Measurement Center Spectral Database

Table 3-3. In-Cell and Flue Gas Concentrations (ppm)
Calculated for Some Compounds Detected in Spectra of Concentrated
Samples Extracted from TNP Unit 2 Coal-Fired Boiler

Run #   Loc    Hydrogen Chloride          Hexane             Formaldehyde            Freon(e)
 (a)    (b)   In-Cell    Flue Gas   In-Cell    Flue Gas   In-Cell    Flue Gas   In-Cell    Flue Gas
-----   ---   -------------------   -------------------   -------------------   -------------------
  1      I                0.000      14.9       0.130      34.9       0.305      16.6       0.144
  2      I     1.62       0.016      3.52       0.035                 0.000                 0.000
  3      I     2.04       0.020      2.79       0.028      6.75       0.067                 0.000
  4      I                0.000      3.29       0.034                 0.000                 0.000
  2      S                0.000      4.41       0.039                 0.000      0.011      0.000
  3      S     3.91       0.035      6.71       0.059                 0.000      0.101      0.001
  4      S     1.23       0.012      2.13       0.021                 0.000      0.216      0.002
 Amb     I                0.000      1.93       0.060                 0.000      0.550      0.017
 Amb     I     5.76       0.217      1.67       0.063                 0.000                 0.000
 Amb     S                0.000      2.23       0.064                 0.000      0.284      0.008
 Amb     S                0.000      2.50       0.066                 0.000                 0.000


Run #   Loc    Hydrogen Cyanide          Methane                Ammonia       
(a)    (b)   In-Cell    Flue Gas   In-Cell    Flue Gas   In-Cell    Flue Gas   
-----   ---   -------------------   -------------------   -------------------
  1      I                0.000      21.5       0.187      16.9       0.147
  2      I                0.000                 0.000      2.26       0.023
  3      I                0.000                 0.000                 0.000
  4      I                0.000                 0.000                 0.000 
  2      S     1.24       0.011                 0.000     0.091       0.001
  3      S     7.26       0.064                 0.000      2.59       0.023
  4      S     1.31       0.013                 0.000                 0.000
 Amb     I                0.000      6.05       0.189      16.4       0.510
 Amb     I                0.000      4.46       0.168                 0.000
 Amb     S                0.000                 0.000      7.75       0.224
 Amb     S                0.000                 0.000      6.84       0.180


        (a) Amb = ambient sample.  Run #1 at the stack was difficult to 
                interpret due to water interference.
        (b) Location designations:
                I = Baghouse Inlet
                S = Stack
        (c) The in-cell concentration is from analysis of the FTIR spectrum.
                Blank spaces indicate a non-detect.
        (d) Flue gas concentration is determined as described in Section 4.6.5.
        (e) Trichlorofluoromethane (CCl3F)
 